Step 3: installing the new power structure – Rockwell Automation 20D PowerFlex 700H/S Frame 13 Replacement Power Structures User Manual

Page 11

Advertising
background image

PowerFlex® 700S and 700H Frame 13 Replacement Power Structures

11

19. Remove the two hexagonal screws that secure the power structure to the

enclosure frame.

20. Follow the instructions in publication PFLEX-IN014…, Installation

Instructions - PowerFlex 700S / 700H High Power Maintenance Stand,
to install the Maintenance Stand (part number 20-MAINSTND).
Remove the power structure by sliding it onto the rails of the
Maintenance Stand.

Note: The Maintenance Stand is designed for removing power
structures from drives supplied in Rittal TS8 enclosures. Alternate
means of removal will be necessary for other types of enclosures.

21. Follow the instructions in publication PFLEX-IN005…, Installation

Instructions - Lifting & Mounting PowerFlex 700S and 700H Drives
(Frame 10 - 14)
, supplied with the new power structure, to lift the power
structure off of the Maintenance Stand.

Step 3: Installing the New
Power Structure

Install the new power structure in reverse order of removal. Refer to the
publication PFLEX-IN006…, Installation Instructions - PowerFlex 700S
and 700H High Power Drives
, for tightening torques of power and motor
terminations.

Remove screws - one each side of enclosure

Advertising
This manual is related to the following products: