Step 1: removing power from the drive – Rockwell Automation 20D PowerFlex 700H/S Frame 13 Replacement Power Structures User Manual

Page 2

Advertising
background image

2

PowerFlex® 700S and 700H Frame 13 Replacement Power Structures

Step 1: Removing Power
From the Drive

1. Turn off and lock out input power. Wait five minutes.

2. Verify that there is no voltage at the drive’s input power terminals.

3. Measure between the +DC and -DC terminals, between the +DC

terminal and the chassis, and between the -DC terminal and the chassis.
The voltage must be zero for all three measurements.

!

ATTENTION: To avoid an electric shock hazard, verify that
the voltage on the bus capacitors has discharged before servicing
the drive. Check the DC bus voltage at the Power Terminal
Block by measuring between the +DC and -DC terminals,
between the +DC terminal and the chassis, and between the -DC
terminal and the chassis. The voltage must be zero for all three
measurements.

Remove power before making or breaking cable connections.
When you remove or insert a cable connector with power
applied, an electrical arc may occur. An electrical arc can cause
personal injury or property damage by:

sending an erroneous signal to your system’s field devices,
causing unintended machine motion

causing an explosion in a hazardous environment

Electrical arcing causes excessive wear to contacts on both the
module and its mating connector. Worn contacts may create
electrical resistance.

L1

L2

L3

O

I

Advertising