Pre-charge connections on, Pre-charge connections on drives with dc input – Rockwell Automation 20D PowerFlex 700H/S Frame 13 Replacement Power Structures User Manual

Page 18

Advertising
background image

18

PowerFlex® 700S and 700H Frame 13 Replacement Power Structures

Pre-Charge Connections on Drives with DC Input

You must connect the ASIC board connectors X9 and X15 to the X50
terminal block for the pre-charge circuit. The X50 terminal block is located
on the Control Frame in the left-hand enclosure. Refer to

Figure 7 on

page 18

for the location of these connection points. Refer to publication

PFLEX-IN006

, Installation Instructions - PowerFlex 700S and 700H

Frame 9-14 Drives, for more information regarding the pre-charge circuit.

X50 Terminal Block Connections

Figure 7 Sample Pre-charge Wiring Diagram

ASIC Board Charge Relay Contact Ratings

ASIC Board
Connector

Terminal

to

X50 Terminal Pre-Charge Circuit Connection Description

X9

25

. . .

1

Pre-charge Complete Signal (+24V DC)

26

. . .

2

Pre-charge Complete Signal (Common)

X15

21

. . .

3

Charge Relay Contact

23

. . .

4

Charge Relay Contact

M

F2

R2 CR2

DC+

DC Source

DC-

CR2

R1

F1

M

ASIC

Board

X9

X15

Precharge
Complete

25
26

21

22
23

CR1

M

CR2

M

CR1

2

X50

1

M

4

3

Charge
Relay*

* Refer to the “ASIC
Board Charge Relay
Contact Ratings” table
below.

External precharge circuitry is shown as dashed lines.

Load

Resistance load (cos

φ

= 1)

Rated load

8 A at 250 VAC: 5 A at 30 VDC

Rated carry current

8 A

Max. switching voltage

250 VAC; 30 VDC, (400 VAC)

Max. switching current

AC 8 A; DC 5 A

Max. switching power

2,000 VA; 150 W

Failure rate (reference value)

5 VDC 10 mA (for gold plating 0.35 µ min.)