Connecting the transducer, Figure d.2 non-contact sensor to channel 1 wiring, Important – Rockwell Automation 1440-VST02-01RA XM-120 Eccentricity Module User Manual
Page 120

Publication GMSI10-UM010C-EN-P - May 2010
112 Wiring Connections for Previous Module Revisions
Connecting the Transducer
The Eccentricity module accepts input from any Allen-Bradley non-contact
eddy current probe. Figures D.2 and D.3 show the wiring of a non-contact
eddy probe to an earlier revision of the XM-120 module (before revision D01).
Figure D.2 Non-Contact Sensor to Channel 1 Wiring
ATTENTION
You may ground the cable shield at either end of the cable.
Do not ground the shield at both ends. Recommended
practice is to ground the cable shield at the terminal base
and not at the transducer. Any convenient Chassis terminal
may be used (see Terminal Block Assignments on page
110).
IMPORTANT
The internal transducer power supply is providing power to
the non-contact sensor.
TYPICAL WIRING FOR NON-CONTACT SENSOR
TO XM-120 ECCENTRICITY MODULE CHANNEL 1
COM
SIG
-24
Channel 1 Input Signal
-24V DC
0
16
22
6
Signal Common
21
5
Jumping terminals
5 to 21 & 6 to 22
configure the
transducer power
supply for -24V DC
powered transducer(s)
Isolated Sensor Driver
Shield
Shield
Floating