Publication GMSI10-UM010C-EN-P - May 2010

46 Configuration Parameters

TIP

The Waveform Period and the Number of Points must
be configured such that the sampling rate (Number of
Points
/Waveform Period) is from 0.32 Hz to 187.5 Hz.
The module will automatically use 187.5 Hz when the
sampling rate is above 93.75, resulting in waveforms
collected with a different period than specified.

The table below shows examples. The entries in the table
are the actual sampling rate (samples per second) and
period corresponding to the waveform period and number
of points.

Note that the signal processing hardware applies a low pass
filter of 20 Hz to the input signal. Therefore the
eccentricity measurements taken at sampling rates above
51.2 samples/second will reflect this low pass filter.

Number of Points

Requested
Period(s)

256

512

1024

2048

Actual
Sampling
Rate

Actual
Period

Actual
Sampling
Rate

Actual
Period

Actual
Sampling
Rate

Actual
Period

Actual
Sampling
Rate

Actual
Period

5

51.2

5.0

187.5

2.73

187.5

5.46

187.5

10.92

10

25.6

10.0

51.2

10.0

187.5

5.46

187.5

10.92

25

10.24

25.0

20.48

25.0

40.96

25.0

81.92

25.0

100

2.56

100.0

5.12

100.0

10.24

100.0

20.48

100.0

800

0.32

800

0.64

800.0

1.28

800.0

2.56

800.0