Publication GMSI10-UM010C-EN-P - May 2010

38 Installing the XM-120 Eccentricity Module

Network Status (NS) Indicator

1

Normal condition when the module is not a slave to an XM-440, PLC, or other master device.

Channel 1, Channel 2, and Tachometer Status Indicators

Eccentricity Indicator

Color

State

Description

No color

Off

Module is not online.

Module is autobauding.

No power applied to the module, look at Module
Status LED.

Green

Flashing

Module is online (DeviceNet) but no connections are
currently established.

1

Solid

Module is online with connections currently
established.

Red

Flashing

One or more I/O connections are in the timed-out state.

Solid

Failed communications (duplicate MAC ID or Bus-off).

Color

State

Description

No color

Off

Normal operation within alarm limits on the channel.

No power applied to the module, look at Module
Status LED.

Yellow

Solid

An alert level alarm condition exists on the channel
(and no transducer fault, tachometer fault, or danger
level alarm condition exists).

Flashing Tach
LED

A tachometer fault (no transducer fault) condition
exists on the tachometer channel

Flashing CH1/2
LED

A tachometer fault condition exists and the channel’s
alarm speed range is enabled (and no transducer fault
on the channel’s transducer).

Red

Solid

A danger level alarm condition exists on the channel
(and no transducer fault or tachometer fault condition
exists).

Flashing

A transducer fault condition exists on the channel.

Color

State

Description

Yellow

Off

Either alarm is actively monitoring the eccentricity
measurement.

Solid

Neither alarm is actively monitoring the eccentricity
measurement. This occurs when both alarms have the
status of DISARM (alarms are disabled, the machine
speed is outside of the alarm’s speed range, or the
module is in Program mode).