Rockwell Automation 1440-VST02-01RA XM-120 Eccentricity Module User Manual
Page 36
Publication GMSI10-UM010C-EN-P - May 2010
28 Installing the XM-120 Eccentricity Module
Figure 2.16 Buffered Output Connections
IMPORTANT
Applies only to XM-120 module revision D01 (and
later).
The voltage operating range of the buffered outputs must
be configured to coincide with the corresponding
transducer bias range. This operating range is configured by
placing a jumper from terminal 5 (channel 1) and terminal
22 (channel 2) to either terminal 6 (Positive Buffer Bias) or
terminal 21 (Buffer -), depending on the transducer. See
Table 2.2. Note the buffered output operating range is
configured independently per channel.
Table 2.2 Configuring Buffered Output Input Range
Transducer
Input Range
Channel
Connect Terminal
To Terminal
Negative Bias
-24 to +9 V
1
5
21
2
22
21
Positive Bias
-5 to +24 V
1
5
6
2
22
6
Non-Bias
-5 to +9 V
1
----
----
2
----
----