♦ Second Press

Displays the aluminum Grounding

conductor size.

♦ Third Press

Displays the NEC table referenced for

the calculation.

fuse/breaker Keys
The ElectriCalc Pro has special keys that automatically calculate the

Amp ratings of the following over-current protection devices: Dual

Element Fuses (Time Delay), Single Element Fuses (Non-Time

Delay), Instantaneous Trip Breakers (Type 1), Inverse Time Breakers

(Type 2), and Overload Protection Devices.
These Fuse and Circuit Breaker sizes are derived using the “Percent

of Full-Load Current” multipliers listed in NEC Table 430.52.
If a parameter is missing or invalid, the calculator will display

none.

overload protection —

♦ First Press

Displays the Overload Amperage requirement

based on the Full-Load Current shown on the

motor nameplate. Multiplies the entered

motor nameplate Full-Load Current

(stored in the  register) by 115% or

the value you enter.
Conforms to NEC Section 430.32(A)(1) value

of 115%, unless you enter another value. For

example, entering 125  would calculate

Overload protection based on 125% of the

entered Amperage.