46 — e
lectri
c
alc
®
P
ro
1. Set to 3-Phase:
(3Ш)
3Ш
3 Ph
2. Enter Volts:
VolT 230.
3. Enter HP:
InD* 50. hP
* If
iND is not shown, press until iND is displayed in the upper left
area of the display.
4. Find Full-Load Current:
flC 130.
a
5. Find Dual Element Fuse size:
aMPs 227.5 de
6. Display percent used:
%flC 175.
%
7. Find Single Element Fuse size:
(SEFuse)
aMPs 390. se
8. Display percent used:
%flC 300.
%
9. Find Inverse Time Circuit Breaker size:
aMPs 325. b2
10. Display percent used:
%flC 250.
%
11. Find Instantaneous Trip Circuit Breaker size:
(InsTrip)
aMPs 1,040. b1
12. Display percent used:
%flC 800.
%