finding Derated Wire size

What is the Derated Wire Size required for nine 75°C Copper wires,

each carrying a maximum load of 65 Amps?

KeysTRoKe

DIsPlay

 

0.

1. Set to 75º C:

 

(75º)

75

0.

2. Set to Copper (if necessary):

 

(Cu/Al)

75 Cu

0.

3. Enter Amps:

  

aMPs 65.

4. Find normal Wire Size:

aWG 6 Cu

WIRe sIZe

5. Find Derated Wire Size:

  

(D/R Size)

D/R 3 Cu

WIRe sIZe

6. Display Wire Ampacity:

D/R 45.5

WIRe a

7. Display Adjustment Factor:

aDJ 70.

%

8. Display NEC Table:

neC 310.15.b.3

sizing Temperature-adjusted Derated Wires

A circuit was built with 60°C Copper wire connecting a 47,650 Volt-

Amp load to a 240 Volt, Three-Phase source. Ambient Temperature

is 50°C. What is the Derated Wire Size required if eight current-

carrying THHN wires are installed in the raceway?

KeysTRoKe

DIsPlay

 

0.