Calculated Industries 5070-A User Guide User Manual
Page 42
Advertising

U
ser
'
s
G
Uide
— 41
(cont’d)
2. Set to 75º C:
(75º C)
3Ø
75
3 Ph
3. Set to Copper (if necessary):
(Cu/Al)
3Ø
75 Cu
3 Ph
4. Enter Amps:
aMPs 20.
5. Enter Volts:
VolT 208.
6. Enter Length:
feeT 175.
7. Enter allowable VD%:
DRoP 3.0
%
V
8. Find Wire Size:
aWG 8 Cu
VD WIRe sIZe
9. Find actual Voltage Drop:
DRoP 4.7 V
10. Find percent Voltage Drop:
DRoP 2.3
% V
finding Voltage Drop Distance
How far from a Three-Phase 240 Volt source can you
install a 15 Amp load using 60°C #10 Copper branch circuit
conductors? Assume a 3% allowable Voltage Drop.
KeysTRoKe
DIsPlay
0.
1. Set to 3-Phase:
(3Ш)
3Ш
3 Ph
KeysTRoKe
DIsPlay