Calculated Industries 5070-A User Guide User Manual
Page 41
Advertising

40 — e
lectri
c
alc
®
P
ro
KeysTRoKe
DIsPlay
0.
1. Set to 3-Phase:
(3Ш)
3Ш
3 Ph
2. Set to 75 º C:
(75º)
3Ø
75
3 Ph
3. Set to Copper (if necessary):
(Cu/Al)
3Ø
75 Cu
3 Ph
4. Enter Amps:
aMPs 20.
5. Enter Volts:
VolT 230.
6. Enter Length (Feet):
feeT 150.
7. Enter Wire Size:
aWG 10 Cu
WIRe sIZe
8. Solve Voltage Drop:
DRoP 6.4
V
9. Solve percent Voltage Drop:
DRoP 2.8
%
V
finding Voltage Drop Wire size
A 20 Amp, Three-Phase 208 Volt load will be located 175 Feet away
from the source. Assuming a 3% allowable Voltage Drop, what is the
size of 75°C conductor required for this branch circuit? What is the
resulting voltage drop?
KeysTRoKe
DIsPlay
0.
1. Set to 3-Phase:
(3Ш)
3Ш
Ph
(cont’d)