finding Voltage Drop Resistance

What is the Resistance of 85 Feet of #2 90° C Copper conductor?

KeysTRoKe

DIsPlay

 

0.

1. Set to 90º C:

 

(90º)

90

0.

2. Set to Copper (if necessary):

 

(Cu/Al)

90 Cu

0.

3. Enter Wire Size:

 

*

aWG 2 Cu

WIRe sIZe

4. Find Resistance:

 

(Wire Res)

ohMs 0.2033993

WIRe

5. Find 85-foot Resistance**:

        

0.0172889

* Wire size can also be entered in Circular Mils (e.g.,

     

enters 10,380 CMILs and displays 10 AWG

Wire Size).

** Given Resistance per 1,000 Feet, divide by 1,000 to get a per

Foot Resistance, then multiply by 85.