Calculated Industries 5070-A User Guide User Manual
Page 40
Advertising

U
ser
'
s
G
Uide
— 39
(cont’d)
KeysTRoKe
DIsPlay
0.
1. Set to 1-Phase:
(1Ш)
1 Ш
1 Ph
2. Set to 75 º C:
(75º)
1 Ø 75
1 Ph
3. Set to Copper (if necessary):
(Cu/Al)
1 Ø 75 Cu
1 Ph
4. Enter Amps:
aMPs 11.
5. Enter Volts:
VolT 208.
6. Enter Length:
feeT 175.
7. Enter Wire Size:
*
aWG 8 Cu
WIRe sIZe
8. Solve Voltage Drop:
DRoP 3.0
V
9. Solve percent Voltage Drop:
DRoP 1.4
%
V
* Wire size can also be entered in Circular Mils (e.g.,
enters 16,510 CMILs and displays
8 AWG Wire Size).
finding Three-Phase Voltage Drop
A 20 Amp, Three-Phase load is being fed by a 230 Volt source
located 150 Feet away. The installation specifications require 75°C
#10 THW stranded Copper conductor. What is the Voltage Drop on
this branch circuit?