Wire sizing based on Insulation Rating

Wiring is being installed in a 240 Volt, Single-Phase system rated at

30 kVA. What is the Wire Size needed if you use 60° C Copper wire?

KeysTRoKe

DIsPlay

 

0.

1. Set to 1-Phase:

 

(1Ш)

1 Ш

1 Ph

2. Set to 60º C:

 

(60º)

1 Ø 60

1 Ph

3. Set to Copper (if necessary):

 

(Cu/Al)

1 Ø 60 Cu

1 Ph

4. Enter kVA:

   

KVa 30.

5. Enter Volts:

   

VolT 240.

6. Find Amps:

aMPs 125.

7. Find Wire Size:

aWG 0

Cu

WIRe sIZe

8. Display Wire Ampacity:

Ø* 125.0

WIRe a

* The Wire Size will be shown in the upper left area of the display when

displaying the Wire Ampacity rating.

9. Display CMIL:

CMIl 105,600.

WIRe

10. Display NEC Table:

neC 310.15.b.16