1. Set to 3-Phase:

 

(3Ш)

3 Ph

2. Set to 75 º C:

 

(75º)

75

3 Ph

3. Set to Copper (if necessary):

 

(Cu/Al)

75 Cu

3 Ph

4. Enter Amps:

  

aMPs 20.

5. Enter Volts:

   

VolT 230.

6. Enter Length (Feet):

   

feeT 150.

7. Enter Wire Size:

  

aWG 10 Cu

WIRe sIZe

8. Solve Voltage Drop:

DRoP 6.4

V

9. Solve percent Voltage Drop:

DRoP 2.8

%

V

finding Voltage Drop Wire size

A 20 Amp, Three-Phase 208 Volt load will be located 175 Feet away

from the source. Assuming a 3% allowable Voltage Drop, what is the

size of 75°C conductor required for this branch circuit? What is the

resulting voltage drop?

KeysTRoKe

DIsPlay

 

0.

1. Set to 3-Phase:

 

(3Ш)

Ph

(cont’d)