5. Find Conduit Size:

IMC 1.25 in

ConD sIZe

* Wire Size can also be entered in Circular Mils (e.g.,

     enters 26,420 CMILs and displays 6 AWG

Wire Size).

finding number of Wires in existing Conduit —

Same Size, Various types

Find the maximum number of #10 THHN Copper wires that can be

pulled through an existing 3 inch EMT Conduit. How many XHHW

wires? How many THW wires?

KeysTRoKe

DIsPlay

 

0.

1. Set to Copper (if necessary):

 

(Cu/Al)

Cu

0.

2. Enter Conduit Type:

  

(Cond Type)

eMT none

ConD

3. Enter Wire Size:

  

*

aWG 10 Cu

WIRe sIZe

4. Enter Conduit Size:

 

eMT 3.00 in

ConD sIZe

5. Find maximum THHN #:

Thhn 167.

TTl WIRes

6. Find maximum XHHW #:

XhhW 145.

TTl WIRes

7. Find maximum THW #:

ThW 145.

TTl WIRes

* Wire Size can also be entered in Circular Mils (e.g.,

     enters 10,380 CMILs and displays 10 AWG

Wire Size).

KeysTRoKe