Calculated Industries 5070-B User Guide User Manual

Page 35

Advertising
background image

34 — e

lectri

c

alc

®

P

ro

Wire sizing based on Material Type

Find the Wire Size for a 75°C Copper Wire carrying a 3Ø load of 265

Amps. What is the equivalent Aluminum Wire Size?

KeysTRoKe

DIsPlay

 

0.

1. Set to 3-Phase:

 

(3Ш)

3 Ph

2. Set to 75º C:

 

(75º)

3Ø 75

3 Ph

3. Set to Copper (if necessary):

 

(Cu/Al)

3Ø 75 Cu

3 Ph

4. Enter Amps:

   

aMPs 265.

5. Find Wire Size:

aWG 300 Cu

WIRe sIZe

6. Change to Aluminum:

 

(Cu/Al)

3Ø 75 al

aWG 400 al

WIRe sIZe

7. Display Wire Ampacity:

4ØØ* 270.0

WIRe a

* The Wire Size will be shown in the upper left area of the display when

displaying the Wire Ampacity rating.

8. Display CMIL:

CMIl 400,000.

WIRe

9. Display NEC Table:

neC 310.15.b.16

Advertising