Re-sizing Wire based on Different Insulation Ratings

What Wire Size is required for a 3Ø, 75°C Copper branch

circuit carrying a load of 260 Amps? What would the Wire Size

be if 90°C Copper is used?

KeysTRoKe

DIsPlay

 

0.

1. Set to 3-Phase:

 

(3Ш)

3 Ph

2. Set to 75º C:

 

(75º)

3Ø 75

3 Ph

3. Set to Copper (if necessary):

 

(Cu/Al)

3Ø 75 Cu

3 Ph

4. Enter Amps:

   

aMPs 260.

5. Find Wire Size:

aWG 300

Cu

WIRe sIZe

6. Change to 90º C:

 

(90º)

3Ø 90 Cu

aWG 0000

Cu

WIRe sIZe

Wire sizing based on ambient Temperature

Find the 90°C Copper Wire Size needed to connect a 47,700

Volt-Amp load to a 240 Volt, Single-Phase source. What is

the adjusted Wire Size, if the Ambient temperature rating is

changed from the default 30°C to 20°C?

KeysTRoKe

DIsPlay

 

0.

1. Set to 1-Phase:

 

(1Ш)

1 Ш

1 Ph