Calculated Industries 5070-B User Guide User Manual

Page 40

Advertising
background image

U

ser

'

s

G

Uide

— 39

(cont’d)

KeysTRoKe

DIsPlay

 

0.

1. Set to 1-Phase:

 

(1Ш)

1 Ш

1 Ph

2. Set to 75 º C:

 

(75º)

1 Ø 75

1 Ph

3. Set to Copper (if necessary):

 

(Cu/Al)

1 Ø 75 Cu

1 Ph

4. Enter Amps:

  

aMPs 11.

5. Enter Volts:

   

VolT 208.

6. Enter Length:

   

feeT 175.

7. Enter Wire Size:

 

*

aWG 8 Cu

WIRe sIZe

8. Solve Voltage Drop:

DRoP 3.0

V

9. Solve percent Voltage Drop:

DRoP 1.4

%

V

* Wire size can also be entered in Circular Mils (e.g.,

     

enters 16,510 CMILs and displays

8 AWG Wire Size).

finding Three-Phase Voltage Drop

A 20 Amp, Three-Phase load is being fed by a 230 Volt source

located 150 Feet away. The installation specifications require 75°C

#10 THW stranded Copper conductor. What is the Voltage Drop on

this branch circuit?