— 35

sizing Parallel Conductors

What size 60°C insulated Copper Wire is required for a single

conductor carrying a 500 Amp load in a Free Air environment (30°C

Ambient Temperature.)? What size for two Parallel conductors? For

three conductors?

KeysTRoKe

DIsPlay

 

0.

1. Set to 60º C:

 

(60º)

60

0.

2. Set to Copper (if necessary):

 

(Cu/Al)

60 Cu

0.

3. Set to Free Air mode:

 

(FrAir)

60 Cu frair

0.

4. Enter Amps:

   

aMPs 500.

5. Find Wire Size for one conductor:

aWG 500 Cu

WIRe sIZe

6. Find Wire Size for two conductors:

 

PaR 000 Cu

WIRe sIZe

7. Find Wire Size for three conductors:

 

PaR 0 Cu

WIRe sIZe

8. Exit Free Air Mode and Clear:

  

60 Cu

0.

Note: Parallel Wire Sizes smaller than 1/0 will be displayed as none.