ro

10. Find total number of Wires:

2.

TTl WIRes

11. Find Conduit Fill Percent:

fIll 24.3

% ConD

12. Find actual Fill Area:

fIll 0.3710

TTl WIRe aRea

13. Find Remaining Area:

ReM 0.1021

WIRe aRea

Note: If a Wire Size has been calculated or stored, and the Wire Type/

quantity is not defined, the calculator will assume 2 THHN wires for

1Ø and 3 THHN wires for 3Ø when calculating Conduit Size.

finding Conduit sizes for Multiple Conductors —

Same Wire type and Size

Find the minimum IMC Conduit Size for eleven #6 THHN Copper

wires.

KeysTRoKe

DIsPlay

 

0.

1. Set to Copper (if necessary):

 

(Cu/Al)

Cu

0.

2. Enter Conduit Type:

  

(Cond Type)

IMC none

ConD

3. Enter Wire Size:

 

*

aWG 6 Cu

WIRe sIZe

4. Enter # THHN:

  

Thhn 11.

WIRes

(cont’d)