3.3.2 EtherNet/IP

Registers

3.3.2 EtherNet/IP on ControlLogix PLC Register Map

The DX80 wireless system is controlled by a ControlLogix PLC using EtherNet/IP through assembly objects and the
Common Industrial Protocol (CIP). Add the SureCross Gateway to the ControlLogix PLC as a “Generic Ethernet Module.”

There is one input assembly object for all DX80 input points and one output assembly object for all DX80 output points.
Each object is 228 elements long, with each element a 16-bit integer.

The SureCross Gateway is configured at the factory to send all inputs and outputs for the first 16 Nodes in the system. To
change the factory settings, change the XML configuration file using the SureCross Web Configurator web pages.

Input Assembly Object, DX80 Input, Instance 100 (0x64). Words are not allocated for any specific unit but are
used, in device order, for each of the device input registers selected using the EIP checkbox.