4 modbus rtu and modbus/tcp register map – Banner SureCross DX80 Wireless Networks User Manual

Page 8

Advertising
background image

2.4 Modbus RTU and Modbus/TCP Register Map

Modbus/TCP and Modbus RTU provide device control and monitoring using holding registers in the 40000 register block.

Each wireless device in the system is allocated 16 holding registers. The Gateway uses the first 16 registers followed by

each Node in the network, based on the Node address. For Node 5, the starting Modbus registers are 1 + (Node# Ч 16) =

1 + (5 Ч 16) = 81, the ending register is 97.

I/O Point

Gateway Modbus Holding Register

Node Modbus Register

1

1

1 + (Node# × 16)

2

2

2 + (Node# × 16)

3

3

3 + (Node# × 16)

4

4

4 + (Node# × 16)

5

5

5 + (Node# × 16)

6

6

6 + (Node# × 16)

7

7

7 + (Node# × 16)

8

8

8 + (Node# × 16)

9

9

9 + (Node# × 16)

10

10

10 + (Node# × 16)

11

11

11 + (Node# × 16)

12

12

12 + (Node# × 16)

13

13

13 + (Node# × 16)

14

14

14 + (Node# × 16)

15

15

15 + (Node# × 16)

16

16

16 + (Node# × 16)

For example:

Registers Device and Input

Connections

Register

Device and Input

Connections

Register

Device and Input

Connections

1

Gateway I/O 1

17

Node 01 I/O 1

33

Node 02 I/O 1

2

Gateway I/O 2

18

Node 01 I/O 2

34

Node 02 I/O 2

3

Gateway I/O 3

19

Node 01 I/O 3

35

Node 02 I/O 3

4

Gateway I/O 4

20

Node 01 I/O 4

...

...

5

Gateway I/O 5

21

Node 01 I/O 5

...

...

6

Gateway I/O 6

22

Node 01 I/O 6

...

...

7

Gateway I/O 7

23

Node 01 I/O 7

...

...

8

Gateway I/O 8

24

Node 01 I/O 8

...

...

9

Gateway I/O 9

25

Node 01 I/O 9

761

Node 47 I/O 9

10

Gateway I/O 10

26

Node 01 I/O 10

762

Node 47 I/O 10

11

Gateway I/O 11

27

Node 01 I/O 11

763

Node 47 I/O 11

12

Gateway I/O 12

28

Node 01 I/O 12

764

Node 47 I/O 12

13

Gateway I/O 13

29

Node 01 I/O 13

765

Node 47 I/O 13

14

Gateway I/O 14

30

Node 01 I/O 14

766

Node 47 I/O 14