I/O 15 Control Messages

Control Code

in Hex (Dec)

Data Field in

Hex (Dec)

Control Code

and Data Field

in Decimal

Restrictions

Description

0x11 (17)

Bit Mask, see

description

4352

0 = all bits off

63 = all bits

on

Gateway Link failure. Set the outputs to default

states based on Bit Mask. Bit0 in the data field =

I/O 9, bit1 = I/O 10, etc. The Gateway Link Failure

flag must be set to enable this feature.

0x12 (18)

00

4608

Host Communication Timeout. Set all outputs on

this device to default states. The Host Link Failure

flag must be set to enable this feature.

0x13 (19)

Bit Mask

4864

Force device sample and report of selected enabled

inputs. The bit mask defines which I/O point will be

sampled. Bit 0 = I/O 1, Bit 1 = I/O 2, etc. A value of

0x3F (63) selects all inputs.

0x20 (32)

Node 0x00

through 0x38

(1–56)

8192+Node#

Gateway Only

Enable Site Survey between Gateway and Node

defined by the data field. All error messages from

the Gateway are ignored when running Site Survey.

Only one Node can participate in Site Survey at any

given time. To disable the Site Survey, use control

code 0x20 with Node 0. A Node must be enabled to

run the Site Survey, then disabled before selecting

the next Node.

0x30 (48)

0x00 through

0x18

12288-12312

FlexPower

Devices only

Enable all switched power outputs. The data field

selects the voltages.

0x00 = turn off

0x05 = 5V

0x07 = 7V

0x0F = 15V

0x14 = 20V

0x18 = 24V

0x31 (49)

12544-12586

Enable switched power #1, data field selects the

voltage (See above)

0x32 (50)

12800-12824

Enable switched power #2, data field selects the

voltage (See above)

0x33 (51)

13056-13080

Enable switched power #3, data field selects the

voltage (See above)

0x34 (52)

13312-13336

Enable switched power #4, data field selects the

voltage (See above)

Example: M-GAGE Baseline

To perform a baseline function on M-GAGE Node 1, write to register 31 (the Node’s register 15).

Reg 31

0x10 (16)

0x00

A baseline function on Node 1 will be initiated. (The command, both bytes together, in decimal would be 4096.)

Example: Forcing a Sample and Report

To force a sample and report of all Node 1’s inputs, write the command and data to register 31.

Host Controller Systems

20