1 host controller systems – Banner SureCross DX80 Wireless Networks User Manual

Page 3

Advertising
background image

1 Host Controller Systems

The Host Controller Systems reference guide contains information about using Modbus RTU, Modbus/TCP, and EtherNet/IP

commands with the SureCross DX80 family of products. This guide includes register maps, control codes, error message

handling, supported function codes, and some sample commands to perform specific tasks. This guide also lists control

codes and sample commands for configuring I/O parameters by writing to Modbus registers.

The SureCross

®

DX80 Gateway uses Modbus RTU, Modbus/TCP, or EtherNet/IP

protocols to communicate with host

controller systems or external devices.

The Modbus Serial Line RTU protocol is a master-slave protocol typically used for industrial applications. Only

one master at any given time is connected to the bus while up to 247 slaves nodes can be connected to the serial

bus.

The Modbus TCP/IP protocol is an open standard implementation of Modbus on Internet protocols. Modbus

TCP/IP is similar to Modbus RTU but transmits information within TCP/IP data packets.

EtherNet/IP is also an application layer protocol for industrial automation. EtherNet/IP is built on the TCP/IP

protocols and uses standard Ethernet hardware.

Modbus is the native protocol for the DX80 wireless system. All wireless devices are organized with a two-byte register for

each I/O point. Sixteen registers are allocated for each device, typically eight registers for inputs and eight registers for

outputs. In the world of Modbus, these registers are addressed consecutively beginning with the Gateway, then Node 1

through Node N.

EtherNet/IP separates the input registers and output registers into blocks. The two blocks of registers, or instances, are

consecutively ordered from the Gateway, then Node 1 through Node 15. The EtherNet/IP interface implementation also

allows for 100 extra input and output registers that can be customized for specific applications.

This configuration guide outlines the procedures involved in configuring I/O parameters by writing to registers. Parameter

configuration using registers can be done with a host system connected to a Gateway, GatewayPro, or Gateway and

Ethernet Bridge combination and any supported protocol.

For more information on Modbus, including basic reference guides, please refer to

www.modbus.org

. For more information

on specific SureCross components, refer to the data sheets for the SureCross devices.

EtherNet/IP is a trademark of ControlNet International, Ltd and Open DeviceNet Vendor Association, Inc.

3

Advertising