Ultra-cut 200 xt – Tweco 200 XT Ultra-Cut Plasma Cutting System User Manual

Page 31

Advertising
background image

ULTRA-CUT 200 XT

Manual 0-5273

INSTALLATION

3-7

A. Electromagnetic Interference (EMI)

Pilot arc starting generates a certain amount of electromagnetic interference (EMI), commonly called RF noise. This

RF noise may interfere with other electronic equipment such as CNC controllers, remote controls, height control-

lers, etc. To minimize RF interference, follow these grounding procedures when installing mechanized systems:

B. Grounding

1. The preferred grounding arrangement is a single point or “Star” ground. The single point, usually on the cut-

ting table, is connected with 1/0 AWG (European 50 mm

2

) or larger wire to a good earth ground (measuring less

than 3 ohms; an ideal ground measures 1 ohm or less. Refer to paragraph ‘C’, Creating An Earth Ground. The

ground rod must be placed as close as possible to the cutting table, ideally less than 10 ft (3.0 m), but no more

than 20 ft (6.1 m) from the cutting table.

NOTE

All ground wires should be as short as possible. Long wires will have increased resistance to RF frequencies. Smaller

diameter wire has increased resistance to RF frequencies, so using a larger diameter wire is better.

2. Grounding for components mounted on the cutting table (CNC controllers, height controllers, plasma remote

controls, etc.) should follow the manufacturer’s recommendations for wire size, type, and connection point

locations.

For Thermal Dynamics components (except Remote Arc Starter and Gas Control Module) it is recommended

to use a minimum of 10 AWG (European 6 mm

2

) wire or flat copper braid with cross section equal to or greater

than 10 AWG connected to the cutting table frame. The Remote Arc Starter uses 1/0 earth ground wire and the

Gas Control Module should use minimum # 4 AWG wire. The connection point must be to clean bare metal;

rust and paint make poor connections. For all components, wires larger than the recommended minimum can

be used and may improve noise protection.

3. The cutting machine frame is then connected to the “Star” point using 1/0 AWG (European 50 mm

2

) or larger

wire.

4. The plasma power supply work cable (see NOTE) is connected to the cutting table at the single point “Star”

ground.

NOTE

Do Not connect the work cable directly to the ground rod. Do not coil up excess ground or power cables. Cut to

proper length and reterminate as needed.

5. Make sure work cable and ground cables are properly connected. The work cable must have a solid connection

to the cutting table. The work and ground connections must be free from rust, dirt, grease, oil and paint. If

necessary grind or sand down to bare metal. Use lock washers to keep the connections tight. Using electrical

joint compound to prevent corrosion is also recommended.

6. The plasma power supply chassis is connected to the power distribution system ground as required by electrical

codes. If the plasma supply is close to the cutting table (see NOTE) a second ground rod is not usually needed,

in fact it could be detrimental as it can set up ground loop currents that cause interference.

When the plasma power supply is far away from the ground rod and interference is experienced, it may help

to install a second earth ground rod next to the plasma power supply. The plasma power supply chassis would

then be connected to this ground rod.

NOTE

It is recommended that the Plasma Power Supply be within 20 - 30 ft (6.1 – 9.1 m) of the cutting table, if possible.

7. The plasma control cable should be shielded with the shield connected only at the cutting machine end. Con-

necting the shield at both ends will allow ground loop currents which may cause more interference than with

no shield at all.

Advertising