08 ground connections, Ground connections -7, Ultra-cut 400 xt – Tweco 400 XT Ultra-Cut Plasma Cutting System User Manual

Page 29

Advertising
background image

ULTRA-CUT 400 XT

Manual 0-5275

INSTALLATION

3-7

3.08 Ground Connections

0 - 10 ft (0 - 3 m) Ideal

20 ft (6 m) Maximum

1/0

Ground Cable

Power Supply

‘Star’

Ground

Earth Ground

Rod

See

Manufacturer

CNC

Device

Torch

Cutting Table

Cutting Machine / Gantry

3/0 Work Cable

Remote Arc

Starter (RAS-1000)

Star Ground on Cutting Table

Note: The gas control module can
be mounted on top of the power
supply.
If it is, it should be grounded
directly to the power supply with
#4 AWG ground, (F).
Any location requires grounding
the power supply to the
‘Star’ ground with the 1/0
Ground Cable (F1).

Gas Control Module

Primary location

#4 AWG

Ground

(F)

Customer supplied

1/0

Ground Cable

(F1)

Art # A-11875

1/0 Ground Cable

A. Electromagnetic Interference (EMI)

Pilot arc starting generates a certain amount of electromagnetic interference (EMI), commonly called RF noise. This RF noise

may interfere with other electronic equipment such as CNC controllers, remote controls, height controllers, etc. To minimize RF

interference, follow these grounding procedures when installing mechanized systems:

B. Grounding

1. The preferred grounding arrangement is a single point or “Star” ground. The single point, usually on the cutting table, is

connected with 1/0 AWG (European 50 mm

2

) or larger wire to a good earth ground (measuring less than 3 ohms; an ideal

ground measures 1 ohm or less. Refer to paragraph ‘C’, Creating An Earth Ground. The ground rod must be placed as close

as possible to the cutting table, ideally less than 10 ft (3.0 m), but no more than 20 ft (6.1 m) from the cutting table.

NOTE

All ground wires should be as short as possible. Long wires will have increased resistance to RF frequencies. Smaller

diameter wire has increased resistance to RF frequencies, so using a larger diameter wire is better.

2. Grounding for components mounted on the cutting table (CNC controllers, height controllers, plasma remote controls, etc.)

should follow the manufacturer’s recommendations for wire size, type, and connection point locations.

For Thermal Dynamics components (except Remote Arc Starter and Gas Control Module) it is recommended to use a minimum

of 10 AWG (European 6 mm

2

) wire or flat copper braid with cross section equal to or greater than 10 AWG connected to the

cutting table frame. The Remote Arc Starter uses 1/0 earth ground wire and the Gas Control Module should use minimum #

4 AWG wire. The connection point must be to clean bare metal; rust and paint make poor connections. For all components,

wires larger than the recommended minimum can be used and may improve noise protection.

3. The cutting machine frame is then connected to the “Star” point using 1/0 AWG (European 50 mm

2

) or larger wire.

4. The plasma power supply work cable (see NOTE) is connected to the cutting table at the single point “Star” ground.

NOTE

Do Not connect the work cable directly to the ground rod. Do not coil up excess ground or power cables. Cut to

proper length and reterminate as needed.

5. Make sure work cable and ground cables are properly connected. The work cable must have a solid connection to the cutting

table. The work and ground connections must be free from rust, dirt, grease, oil and paint. If necessary grind or sand down

Advertising