09 connect coolant leads, Connect coolant leads -9, Ultra-cut 400 xt – Tweco 400 XT Ultra-Cut Plasma Cutting System User Manual

Page 31

Advertising
background image

ULTRA-CUT 400 XT

Manual 0-5275

INSTALLATION

3-9

This test assumes the 115 or 230 VAC source neutral is connected to the utility earth ground.

Art # A-07252

WARNING

Use extreme caution. This

test uses live voltage.

NEUTRAL

Earth Grounded

HOT

On 115V AC Line:

3VAC = 3 ohms

1VAC = 1 ohm

On 230V AC Line:

1.5VAC = 3 ohms

0.5VAC = 1 ohm

Ground Rod

with other

connections removed

100W Incandescent

light bulb*

* Can replace light bulb with

a 100w resistor.

Use 100 ohm for 115VAC.

Use 500 ohm for 230VAC

NEUTRAL

PROBE

VAC

HOT

PROBE

Ground Testing

2. Increasing the ground rod length beyond 20 - 30 ft (6.1 – 9.1 m) does not generally increase the effectiveness of the ground

rod. A larger diameter rod which has more surface area may help. Sometimes keeping the soil around the ground rod moist

by continuously running a small amount of water into it will work. Adding salt to the soil by soaking it in salt water may also

reduce its resistance. You may also try a chemical ground rod devise. When these methods are used, periodic checking of

the ground resistance is required to make sure the ground is still good.

D. Routing Of Torch Leads

1. To minimize RF interference, position torch leads as far as possible from any CNC components, drive motors, control cables,

or primary power lines. If cables have to pass over torch leads, do so at an angle. Do not run the plasma control or other

control cables in parallel with the torch leads in power tracts.

2. Keep torch leads clean. Dirt and metal particles bleed off energy, which causes difficult starting and increased chance of RF

interference.

3.09 Connect Coolant Leads

1. Connect the color-coded coolant hoses to the coolant connections on the power supply rear panel. The supply line (out)

is flagged green, the return line (in) is flagged red.