PROBLEMS/SERVICE

TRANSMIG 250i

Manual 0-5187

5-3

PROBLEMS AND ROUTINE SERVICE

5.02 Routine Service and Calibration Requirements

!

WARNING

There are extremely dangerous voltage and power levels present inside this Inverter Power Source. Do

NOT attempt to open or repair unless you are an accredited CIGWELD Service Provider. Disconnect the

Welding Power Source from the Mains Supply Voltage before disassembling.

Routine Inspection, Testing & Maintenance

The inspection and testing of the power source and associated accessories shall be carried out in accordance with

Section 5 of AS 1674.2 - 2007: Safety in Welding and Allied Processes-Part 2 Electrical. This includes an insula-

tion resistance test and an earthing test to ensure the integrity of the unit is compliant with Cigweld's original

specifications.
If equipment is to be used in a hazardous location or environments with a high risk of electrocution as outlined in

AS 1674.2 - 2007, then the above tests should be carried out prior to entering this location.

A. Testing Schedule

1. For transportable equipment, at least once every 3 months; and
2. For fixed equipment, at least once every 12 months.

The owners of the equipment shall keep a suitable record of the periodic tests and a system of tagging, includ-

ing the date of the most recent inspection.

A transportable power source is deemed to be any equipment that is not permanently connected and fixed in

the position in which it is operated.

B. Insulation Resistance

Minimum insulation resistance for in-service CIGWELD Inverter Power Sources shall be measured at a volt-

age of 500V between the parts referred to in Table 5-2 below. Power sources that do not meet the insulation

resistance requirements set out below shall be withdrawn from service and not returned until repairs have

been performed such that the requirements outlined below are met.

Components to be Tested

Minimum Insulation

Resistance (MΩ)

Input circuit (including any connected control circuits) to welding circuit

(including any connected control circuits)

5

All circuits to exposed conductive parts

2.5

Welding circuit (including any connected control circuits) to any auxiliary

circuit which operates at a voltage exceeding extra low voltage

10

Welding circuit (including any connected control circuits) to any auxiliary

circuit which operates at a voltage not exceeding extra low voltage

1

Separate welding circuit to separate welding circuit

1

Table 5-2: Minimum Insulation Resistance Requirements: CIGWELD Inverter Power Sources