Air pressure tubing – Carrier 50FK User Manual

Page 23

Advertising
background image

Table 7 — Switch Functions

SWITCH

NUMBER

CONFIGURATION

VOLTAGE

FUNCTION

SW-1

N.C.

115

Deenergize 115-v (OFC, Comp, IFC, Electric Heaters)

SW-2

N.C.

115

Deenergize TRAN7 (Process Board)

SW-3

N.O.

24

Energize EOR (Open Economizer Outside Air Dampers)

SW-4

N.O.

115

Energize IFC and CR-3 (IGV/VFD)

SW-5

N.C.

115

Isolate IFC and PEC for Separate Operation

SW-6

N.O.

115

Energize PEC (Power Exhaust)

SW-7

N.O.

24

Open PED at DPS

SW-8

N.C.

24

Block Auto-Close at DPS (Due to Low BP)

SW-9A/B

A: N.O.
B: N.C.

115 max

Signal Room Terminals to Open (HIR1)

LEGEND

BP

Building Pressure

DPS — Differential Pressure Switch
EOR — Economizer Open Relay
HIR

Heat Interlock Relay

IFC

Indoor Fan Contactor

IGV

Inlet Guide Vane

N.C. — Normally Closed
N.O. — Normally Open
PEC — Power Exhaust Contactor
PED — Power Exhaust Damper
OFC — Outdoor Fan Contactor
VFD — Variable Frequency Drive

Air Pressure Tubing —

Before options such as inlet

guide vanes (IGV), variable frequency drive (VFD), and/or
modulating power exhaust can operate properly, the pneu-
matic tubing for pressure sensing must be installed. Use fire-
retardent plenum tubing (field-supplied). Tubing size depends
on type of control device (see Table 8 below). Tubing must
be run from the appropriate sensing location (in the duct or
in the building space) to the control device location in the
unit.

Table 8 — Tubing Size

OPTION

UNITS

NOMINAL TUBE

SIZE (in.)

Inlet Guide Vanes (IGV)

ALL

3

8

Variable Frequency

Drive (VFD)

ALL

1

4

Modulating Power Exhaust FK,FKX,JK,JKX

3

8

INLET GUIDE VANES — The tubing for the duct pressure
(DP) control option should sample supply duct pressure about

2

3

of the way out from the unit in the main trunk duct, at a

location where a constant duct pressure is desired.

The inlet guide vanes are controlled by a differential pres-

sure switch (DPS). On sizes 034-048, the DPS is located in
the auxiliary control box at the economizer end of the unit
(see Fig. 33). On sizes 054-104, the DPS is located in the
supply fan section. See Fig. 34. Use a nominal

3

8

-in. plastic

tubing.

VARIABLE FREQUENCY DRIVE — The tubing for the
duct pressure (DP) control option should sample supply duct
pressure about

2

3

of the way out from the unit in the main

trunk duct, at a location where a constant duct pressure is
desired.

The duct pressure is sensed by a pressure transducer. The

pressure transducer output is directed to the VFD. On 034-
048 units the DP transducer is located in the auxiliary con-
trol box. On 054-104 units, the DP transducer is located in
the supply fan section. See Fig. 34. Use a nominal

1

4

-in.

plastic tubing.

23