Carrier 50FK User Manual

Page 42

Advertising
background image

Table 19 — Compressor Loading and Unloading Sequences

COOLING

STAGE

SIZE 034 UNITS

Lead Circuit

Lag Circuit

Active

Cylinders

Percent

Capacity

Comp 1

Unloader

U1

Unloader

U2

Comp 2

0

OFF

OFF

OFF

OFF

0

0

1

ON

ON

ON

OFF

2

17

2

ON

ON

OFF

OFF

4

33

3

ON

OFF

OFF

OFF

6

50

4

ON

ON

ON

ON

8

67

5

ON

ON

OFF

ON

10

83

6

ON

OFF

OFF

ON

12

100

COOLING

STAGE

SIZE 038 UNITS

Lead Circuit

Lag Circuit

Active

Cylinders

Percent

Capacity

Comp 1

Unloader

U1

Unloader

U2

Comp 2

0

OFF

OFF

OFF

OFF

0

0

1

ON

ON

ON

OFF

2

14

2

ON

ON

OFF

OFF

4

28

3

ON

OFF

OFF

OFF

6

42

4

ON

ON

ON

ON

6

72

5

ON

ON

OFF

ON

8

86

6

ON

OFF

OFF

ON

10

100

COOLING

STAGE

SIZE 044 UNITS

Lead Circuit

Lag Circuit

Active

Cylinders

Percent

Capacity

Comp 1

Unloader

U1

Comp 2

0

OFF

OFF

OFF

0

0

1

ON

ON

OFF

2

25

2

ON

OFF

OFF

4

50

3

ON

ON

ON

6

75

4

ON

OFF

ON

8

100

COOLING

STAGE

SIZE 048 UNITS

Lead Circuit

Lag Circuit

Active

Cylinders

Percent

Capacity

Comp 1

Unloader

U1

Unloader

U2

Comp 2

0

OFF

OFF

OFF

OFF

0

0

1

ON

ON

ON

OFF

2

19

2

ON

ON

OFF

OFF

4

38

3

ON

OFF

OFF

OFF

6

58

4

ON

ON

ON

ON

6

62

5

ON

ON

OFF

ON

8

81

6

ON

OFF

OFF

ON

10

100

42

Advertising
This manual is related to the following products: