Table 29 — Carrier Default Program Parameter Values

PARAMETER GROUP

PARAMETER

DEFAULT VALUE

SEtP

(Setup)

ACC1

60.0 Sec

DEC1

60.0 Sec

UL

60.0 Hz

LL

10.0 Hz*

Luln

1

P3

20%

F-P3

0.0 Hz

P4

100%

F-P4

60 Hz

tHr1

See Table 31

StC1

0

StL1

110%

OLN

1

tYP

5*

Gr.F

(Fundamental)

FH

60 Hz

Pt

2

Gr.Fb

(Feedback)

FbP1

1*

Fbln

2

GP

.30

Gl

2 sec

GA

0

GFS

80

P1LL

10

PuL

1

PuUl

10

PuLL

10

Gr.SF

(Frequency Settings)

Fsor

60 Hz

Sr.n

1* (054-104 only)

SrN1

0* (054-104 only)

Gr.Pn

(Panel Control)

Fr

0*

Gr.St

(Terminal Selection)

1t

1

1t0

0

1t1

56

1t2

13

1t3

3

1t4

10

Gr.Pr

(Protection)

UuC

1*

UuCt

2

ArSt

3

Gr.Ut

(Utility)

Cnod

1*

bLSF

1* (054-104 only)

Fnod

2*

bLPn

1*

*These settings differ from the Toshiba defaults and are required for Carrier applications.

NOTE: To restore original factory settings, change tYP to 6 in Setup mode (SetP). This restores the VFD original factory settings.