Fig. 48 — processor board test points, Fig. 49 — relay board test points 48 – Carrier 50FK User Manual

Page 48

Advertising
background image

These 2 steps will help determine if a component other

than a board is at fault or if the problem is external to control
circuit.

A volt-ohmmeter will be needed to troubleshoot boards. A

digital meter is preferred but a Simpson 260 or equivalent
will work.

To prevent damage to solid-state electronic components
on boards, meter probes should only be placed on ter-
minals and test points listed in following sections. Do
not short the electrical components, and use extreme care
while working on the processor board.

PROCESSOR BOARD CHECKOUT — Refer to Fig. 48
and 49 for location of terminal pins and test points.

Step 1 — Check Transformer Input to the Board — Connector
J4 is used to connect the control transformer to the processor
board.
1. Set the volt-ohmmeter to ac voltage with a range setting

of approximately 30 v.

2. Turn control switch to ON position.
3. Check voltage at following terminals on pin terminal con-

nector J4:

TERMINALS

VOLTAGE (AC)

1 to 2

15.3 to 20.9

4 to 6

16.2 to 22.0

5 to 6

8.1 to 11.0

5 to 4

8.1 to 11.0

4. If voltage is not within range, check primary side.

115-v transformer — 104 to 127 vac
230-v transformer — 207 to 254 vac

5. If primary voltage is not correct, check system fuse, trans-

former, ON-OFF switch, and wiring. If these are okay,
contact power company.

6. If primary voltage is correct, but secondary voltage

(24 v ± 10%) is incorrect, replace transformer.

7. Turn control switch to OFF position.
Step 2 — Check Processor Board Power Supply
1. Set meter to approximately 20 vdc.
2. Turn power to OFF position.
3. Connect negative lead to TP18.
4. Turn power switch to ON position and press display but-

ton to enter Quick Test mode.

5. Check voltage between TP18 and each of the following

test pins:

TEST PIN

VOLTAGE (DC)

TP3

ϩ

10

TP4

ϩ

12

TP6

ϩ

5

TP10

ϩ

5

TP14

ϩ

12

TP15

ϩ

12

TP7

−5*

*If not using a digital meter, leads must be reversed.

6. If voltage is incorrect, replace processor board.
7. Turn power to ON position.

Step 3 — Check Voltage Tolerance Circuitry
1. Turn power to OFF position.
2. Negative test probe on TP18 and system in Quick Test

mode.

3. Check voltage TP18 to TP9.
4. If voltage is greater than

ϩ1 vdc, recheck transformer

input voltage.

5. If transformer is okay, replace processor board.
6. Turn power to ON position.
Step 4 — Check Processor Reset Line
1. Turn power to OFF position.
2. Negative probe on TP18.
3. Check voltage TP18 to TP11.
4. If voltage is greater than

ϩ3 vdc, reset power and

recheck.

5. If voltage is still incorrect, replace processor board.
6. Turn power to ON position.

LEGEND

J

Pin Terminal Strip

TP — Test Pin

Fig. 48 — Processor Board Test Points

K1

K2

K3

C1

C2

C3

C4

C5

C6

C7

C8

CR1

CR2

CR3

CR4

CR5

CR6

CR7

CR8

C27

C15

C14

C26

C25

C24

C23

C22

E3

CR9

CR10

CR11

CR12

CR13

C9

C10

C11

C12

C13

R9

R10

R11

R12

R13

J5

J6

C19

C16

C18

C21

LEGEND

CR — Control Relay
J

Pin Terminal Strip

K

Relay

Fig. 49 — Relay Board Test Points

48