background image

Table 2 — Pin Terminal Connector J2

Status Switch Inputs

CONNECTOR J2

TERMINAL NO.

STATUS SWITCH

UNIT SIZE

034-104

1,2

Oil Pressure,

Circuit 2

Jumpered

3,4

Oil Pressure,

Circuit 1

Jumpered

7,8

Loss Of Charge,

Circuit 2

LPS2

9,10

Loss of Charge,

Circuit 1

LPS1

13,14

Economizer

Changeover

EC

15,20

Compressor Fault

Signal

CR2

15,24

Compressor Fault

Signal

CR1

LEGEND

CR

Control Relay

EC

Enthalpy Control

LPS — Low-Pressure Switch

NOTE: Terminal numbers 5, 6, 11, 12, 16-19, and 21-23 are not used

on these units.

LEGEND

T

Thermistor
Field Wiring
Accessory

Fig. 2 — Pin Terminal Connector J1

Thermistor Inputs

LEGEND

CR

Control Relay

EC

Enthalpy Control

LPS — Low-Pressure Switch

Fig. 3 — Pin Terminal Connector J2

Status Switch Inputs

LEGEND

IN

Input

Factory Wiring

P

Potentiometer

Field Wiring

RNT — Return

Accessory

SW

Switch

Fig. 4 — Pin Terminal Connector J3

Potentiometer Inputs

4