Table 3 — Output Pin and Terminal Assignments

OUTPUT PIN-

TERMINAL

NAME

RATING

DEVICE

J6-1

Stage 1
Compressor Relay (K1)*

24 vac

CR1

J6-2

Stage 2
Compressor Relay (K2)*

U2**

J6-3

Stage 3
Compressor Relay (K3)*

U1

J6-4

Stage 4
Compressor Relay (K4)†

Not Used

J6-5

Stage 5
Compressor Relay (K5)†

CR2

J6-6

Stage 6
Compressor Relay (K6)†

Not Used

J6-7

Economizer Open Relay (K7)

EOR

J6-8

Economizer Close Relay (K8)

ECR

J5-1

Supply Fan Relay (K9)

115 vac

IFC

J5-2

Morning Warm-Up Relay (K10)

HIR

J5-3

Stage 1 Condenser
Fan Relay (K11)

OFC2/OFC3 ††

J5-4

Stage 2 Condenser
Fan Relay (K12)

OFC4

J5-5

External Alarm Relay (K13)

ALM

LEGEND

ALM — Alarm
CR

Control Relay

ECR — Economizer Close Relay
EOR — Economizer Open Relay
HIR

Heat Interlock Relay

IFC

Indoor (Evaporator) Fan Contactor

OFC — Outdoor (Condenser) Fan Contactor
U

Unloader

*Circuit 1.

†Circuit 2.

**U2 is not used on 044 units.

††OFC2 on 034-048 units; OFC3 on 054-104 units.

Used on 054-104 units only.

LEGEND

CR — Control Relay
J

Terminal Pin Connectors

K

Relay

Fig. 5 — Relay Board