DV360/580 Series Direct Vent Gas Fireplace

20010667

Optional Top Vent Application

The DV360/580 fireplace is shipped as a rear vent unit.
If the layout requires a top vent, convert the unit follow-
ing the steps below.
1. Remove the 10 screws securing outer collar adapter

to fireplace. (Fig. 11)

2. Set outer collar adapter aside.
3. Remove insulation from top of unit and discard. Re-

move the four (4) screws securing flue cover to top
of unit and remove flue cover. (Fig. 12)

4. Remove the four (4) screws securing flue pipe to

back of unit. Remove flue pipe. (Fig. 12)

5. Secure flue cover to back of flue outlet. Be sure to

replace gasket. (Fig. 14)

6. Install flue pipe and gasket removed in step 4 to top

of unit with four (4) screws. Be sure to replace gas-
ket. (Fig. 14)

7. Secure outer collar adapter to unit with the round

collar on top, secure with 10 screws.

NOTE: Be sure not to damage any gasket material.

FP1030

Outer Collar Adapter

Flue Pipe

2/16/00 djt

Outer

Collar

Adapter

Flue

Pipe

Remove

Screws

(5)

Remove Screws

(5)

FP1030

Fig. 11 Remove screws from outer collar adapter.

FP1027

DV360/580

Outer Collar Adapter

Flue Pipe

1/27/00 djt

Insulation

Flue
Cover

Flue

Pipe

Remove

Screws

(4)

Remove Screws (4)

FP1027

Fig. 12 Remove flue cover and flue pipe.

CAUTION: Remove insulation. Insulation extends

beyond opening in top of unit. Be sure to
remove all insulation before completing
conversion. Insulation measures 9¹⁄₄” x
22³⁄₄” (23.5 cm x 57.8 cm). If the unit is con-
verted back to a rear vent, the insulation

(Part number 20003129) must be replaced.

DVT584-604

Outer Collar Adapter

Flue Pipe

3/11/99 djt

Flue Pipe

Replace

Screws (4)

Replace

Screws

(4)

Flue Cover

FP1028

Fig. 13 Replace flue cover and flue pipe.

FP1031

Outer Collar Adapter

Flue Pipe completed

2/16/00 djt

FP1031

Fig. 14 Complete conversion.

After conversion to top vent configuration,
the 4” (102 mm) flue pipe should be con-
centric within the 7” (175 mm) outer collar.