Fig. 13 -- Single--Stage Gas Valve

If larger adjustments are required, change main burner orifices
following the recommendations of national and local codes.
NOTE:

All other appliances that use the same meter must be

turned off when gas flow is measured at the meter.
Proceed as follows:

1. Turn off gas supply to unit.
2. Remove pipe plug on manifold (See Fig. 11) and connect

manometer. Turn on gas supply to unit.

3. Record number of seconds for gas meter test dial to make

one revolution.

4. Divide number of seconds in Step 3 into 3600 (number of

seconds in one hr).

5. Multiply result of Step 4 by the number of cubic feet (cu ft)

shown for one revolution of test dial to obtain cubic feet (cu

ft) of gas flow per hour.

6. Multiply result of Step 5 by Btu heating value of gas to

obtain total measured input in Btuh. Compare this value
with heating input shown in Table 3 (Consult the local gas
supplier if the heating value of gas is not known).

EXAMPLE: Assume that the size of test dial is 1 cu ft, one
revolution takes 32 sec, and the heating value of the gas is 1050

Btu/ft

3

. Proceed as follows:

1. 32 sec. to complete one revolution.
2. 3600 ÷ 32 = 112.5.
3. 112.5 x 1 =112.5 ft

3

of gas flow/hr.

4. 112.5 x 1050 = 118,125 Btuh input.

If the desired gas input is 115,000 Btuh, only a minor change in the

manifold pressure is required.
Observe manifold pressure and proceed as follows to adjust gas

input:

1. Remove regulator cover screw over plastic adjustment

screw on gas valve (See Fig. 13).

2. Turn plastic adjustment screw clockwise to increase gas

input, or turn plastic adjustment screw counterclockwise to
decrease input (See Fig. 13). Manifold pressure must be

between 3.2 and 3.8 IN. W.C.

FIRE AND UNIT DAMAGE HAZARD
Failure to follow this warning could result in personal

injury or death and/or property damage.
Unsafe operation of the unit may result if manifold pressure

is outside this range.

!

WARNING

3. Replace regulator cover screw on gas valve (See Fig. 13).
4. Turn off gas supply to unit. Remove manometer from

pressure tap and replace pipe plug on gas valve. (See Fig.
11.) Turn on gas to unit and check for leaks.

Measure Manifold Pressure (Propane Units)
Refer to propane kit installation instructions for properly checking
gas input.
NOTE: For installations below 2,000 ft (610 m), refer to the unit
rating plate for proper propane conversion kit. For installations
above 2,000 ft (610 m), contact your distributor for proper propane
conversion kit.

Check Burner Flame

With control access panel (see Fig. 19) removed, observe the unit
heating operation. Watch the burner flames to see if they are light

blue and soft in appearance, and that the flames are approximately
the same for each burner. Propane will have blue flame (See Fig.

12). Refer to the Maintenance section for information on burner

removal.

Normal Operation

An LED (light--emitting diode) indicator is provided on the

integrated gas unit controller (IGC) to monitor operation. The IGC

is located by removing the control access panel (see Fig. 19).
During normal operation, the LED is continuously on (See Table 5

for error codes).

Airflow and Temperature Rise

The heating section for each size unit is designed and approved for

heating operation within the temperature--rise range stamped on the

unit rating plate.
Table 10 shows the approved temperature rise range for each

heating input, and the air delivery cfm at various temperature rises
for a given external static pressure. The heating operation airflow

must produce a temperature rise that falls within the approved

range.
Refer to Indoor Airflow and Airflow Adjustments section to adjust

heating airflow when required.

Limit Switches

Normally closed limit switch (LS) completes the control circuit.
Should the leaving--air temperature rise above the maximum

allowable temperature, the limit switch opens and the control
circuit “breaks.” Any interruption in the control circuit instantly

closes the gas valve and stops gas flow to the burners and pilot.
The blower motor continues to run until LS resets.
When the air temperature at the limit switch drops to the

low--temperature setting of the limit switch, the switch closes and

48V