48v t -- a – Carrier 48VT(N) User Manual

Page 23

Advertising
background image

23

Table 10 -- Dry Coil Air Delivery* -- Horizontal and Downflow Discharge -- Unit 48VT--A24--60 Cont

UNIT

HEATING

RISE

RANGE

MOTOR

SPEED

WIRE

COLOR

EXTERNAL STATIC PRESSURE (in. W.C.)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

48VT(-,N)A60115

30 - 60

o

F

(17 - 33

o

C)

Low

Blue

CFM

1448

1362

1296

1226

1168

1108

1071

998

905

Heating

Rise (

o

F)

60

NA

NA

NA

NA

NA

NA

NA

NA

Heating

Rise (

o

C)

33

NA

NA

NA

NA

NA

NA

NA

NA

Med-Low

Pink

CFM

1722

1675

1614

1543

1499

1442

1408

1356

1308

Heating

Rise (

o

F)

50

52

54

56

58

60

NA

NA

NA

Heating

Rise (

o

C)

28

29

30

31

32

33

NA

NA

NA

Medium

2

Red

CFM

1887

1847

1783

1726

1677

1625

1578

1527

1432

Heating

Rise (

o

F)

46

47

49

50

52

53

55

57

NA

Heating

Rise (

o

C)

26

26

27

28

29

30

31

32

NA

Med-High

1

Orange

CFM

2055

2008

1958

1927

1900

1768

1685

1581

1458

Heating

Rise (

o

F)

42

43

44

45

46

49

52

55

60

Heating

Rise (

o

C)

23

24

25

25

25

27

29

31

33

High

Black

CFM

2292

2238

2158

2049

1935

1840

1732

1635

1513

Heating

Rise (

o

F)

38

39

40

42

45

47

50

53

57

Heating

Rise (

o

C)

21

22

22

24

25

26

28

30

32

48VT(-,N)A60130

35 - 65

o

F

(19 - 36

o

C)

Low

Blue

CFM

1448

1321

1282

1235

1192

1145

1101

1057

1011

Heating

Rise (

o

F)

NA

NA

NA

NA

NA

NA

NA

NA

NA

Heating

Rise (

o

C)

NA

NA

NA

NA

NA

NA

NA

NA

NA

Med-Low

Pink

CFM

1722

1675

1614

1543

1499

1442

1408

1356

1308

Heating

Rise (

o

F)

56

57

60

62

64

NA

NA

NA

NA

Heating

Rise (

o

C)

31

32

33

35

36

NA

NA

NA

NA

Medium

2

Red

CFM

1887

1847

1783

1726

1677

1625

1578

1527

1432

Heating

Rise (

o

F)

51

52

54

56

57

59

61

63

NA

Heating

Rise (

o

C)

28

29

30

31

32

33

34

35

NA

Med-High

1

Orange

CFM

2055

2008

1958

1927

1900

1768

1685

1581

1458

Heating

Rise (

o

F)

47

48

49

50

51

54

57

61

NA

Heating

Rise (

o

C)

26

27

27

28

28

30

32

34

NA

High

Black

CFM

2292

2238

2158

2049

1935

1840

1732

1635

1513

Heating

Rise (

o

F)

42

43

45

47

50

52

56

59

64

Heating

Rise (

o

C)

23

24

25

26

28

29

31

33

35

* Air delivery values are without air filter and are for dry coil (See 48VT---A Wet Coil Pressure Drop table).