48v t -- a – Carrier 48VT(N) User Manual

Page 35

Advertising
background image

35

Table 11 – Troubleshooting Guide -- Cooling or Heat Pump Heating Mode

SYMPTOM

CAUSE

REMEDY

Compressor and Outdoor fan will not

start.

Power Failure

Call power company.

Fuse blown or circuit breaker tripped

Replace fuse or reset circuit breaker.

Defective thermostat, contactor, transformer, or control

relay

Replace component.

Insufficient line voltage

Determine cause and correct.

Incorrect or faulty wiring

Check wiring diagram and rewire correctly.

Thermostat setting too high

Lower thermostat setting below room temperature.

Compressor will not start but Outdoor

fan runs.

Faulty wiring or loose connections in compressor circuit

Check wiring and repair or replace.

Compressor motor burned out, seized, or internal over-

load open

Determine cause Replace compressor.

Defective run/start capacitor, overload, start relay

Determine cause and replace.

One leg of 3---phase power dead

Replace fuse or reset circuit breaker. Determine

cause.

Three---phase scroll compressor makes

excessive noise, and there may

be a low pressure differential.

Scroll compressor is rotating in the wrong direction

Correct the direction of rotation by reversing the

3---phase power leads to the unit.

Compressor cycles (other than normally

satisfying thermostat).

Refrigerant overcharge or undercharge

Recover refrigerant, evacuate system, and recharge

to capacities shown on nameplate.

Defective compressor

Replace and determine cause.

Insufficient line voltage

Determine cause and correct.

Blocked Outdoor

Determine cause and correct.

Defective run/start capacitor, overload or start relay

Determine cause and replace.

Defective thermostat

Replace thermostat.

Faulty Outdoor---fan motor or capacitor

Replace.

Damaged reversing valve

Determine cause and correct

Restriction in refrigerant system

Locate restriction and remove.

Compressor operates continuously.

Dirty air filter

Replace filter.

Unit undersized for load

Decrease load or increase unit size.

Thermostat set too low

Reset thermostat.

Low refrigerant charge

Locate leak, repair, and recharge.

Mechanical damage in compressor.

Replace compressor.

Air in system

Recover refrigerant, evacuate system, and recharge.

Frosted coil with incorrect defrost operation

Check defrost time settings, Reset as necessary

Check defrost temperature switch, Replace as nec-

essary

Outdoor coil dirty or restricted

Clean coil or remove restriction .

Excessive head pressure.

Dirty air filter

Replace filter.

Dirty Indoor or Outdoor coil

Clean coil.

Refrigerant overcharged

Recover excess refrigerant.

Air in system

Recover refrigerant, evacuate system, and recharge.

Indoor or Outdoor air restricted or air short---cycling

Determine cause and correct.

Head pressure too low.

Low refrigerant charge

Check for leaks, repair, and recharge.

Compressor IPR leaking

Replace compressor.

Restriction in liquid tube

Remove restriction.

Excessive suction pressure.

High heat load

Check for source and eliminate.

Compressor IPR leaking

Replace compressor.

Refrigerant overcharged

Recover excess refrigerant.

Reversing valve hung up or leaking internally

Replace valve

Suction pressure too low.

Dirty air filter

Replace Filter.

Low refrigerant charge

Check for leaks, repair, and recharge.

Metering device or low side restricted

Remove source of restriction.

Insufficient Indoor airflow

Increase air quantity. Check filter — replace if neces-

sary.

Temperature too low in conditioned area

Reset thermostat.

Outdoor ambient below 55°F (12.8°C)

Install low---ambient kit.

Field---installed filter---drier restricted

Replace.

(Heat) Outdoor coil frosted

Move timer on control board to 30 minutes between

defrost cycles

Compressor runs but outdoor fan does

not

NC (normally closed) contacts on defrost board open

Check condition of relay on board Replace if neces-

sary

48V

T

--

A

Advertising