Large curb, Small curb roof curb detail, 48v t -- a – Carrier 48VT(N) User Manual

Page 5

Advertising
background image

5

C

B

A

F

D

E

LARGE CURB

C

B

A

F

D

E

SMALL CURB

ROOF CURB DETAIL

Wood nailer*

Roofcurb*

Insulation
(field supplied)

*Provided with roofcurb

Cant strip
field supplied

Roofing material
field supplied

Flashing field
supplied

HVAC unit
base rails

Roofcurb

Sealing
Gasket

HVAC unit
basepan

Anchor screw

A09090

A09095

A09110

A09111

UNIT SIZE

CATALOG

NUMBER

A

IN. (mm)

B

IN. (mm)*

C

IN. (mm)

D

IN. (mm)

E

IN. (mm)

F

IN. (mm)

Small

CPRFCURB010A00

11 (279)

10 (254)

16 (406)

47.8 (1214)

32.4 (822)

2.7 (69)

CPRFCURB011A00

14 (356)

Large

CPRFCURB012A00

11 (279)

14 (356)

43.9 (1116)

CPRFCURB013A00

14 (356)

NOTES:

1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as required, to unit being installed.
3. Roof curb is made of 16--gauge steel.
4. Attach ductwork to curb (flanges of duct rest on curb).
5. Insulated panels: 1--in. (25.4 mm) thick fiberglass 1 lb. density.

IMPORTANT: Do not install large base pan HYBRID HEAT
units onto the small base pan (common curb). The center of gravity
on a large base pan HYBRID HEAT unit could overhang the curb
causing an unsafe condition. Before installing any large base pan
unit onto the common curb, check the “Y” distance in the product

literature dimensional drawing to ensure that “Y” is greater than 14
in. (356 mm). Do not install any large base pan unit onto the
common curb with a “Y” dimension (center of gravity) less than 14
in. (356 mm).

Fig. 4 -- Roof Curb Dimensions

48V

T

--

A