Carrier 48VT(N) User Manual

Page 28

Advertising
background image

28

Integrated
Gas Unit
Controller
(IGC)

Induced Draft
Motor

Rollout
Switch

Mounting
Screw

Burner
Rack

Inducer
Blower
Housing

Flue
Collector
Box

Interface Fan
Board (IFB)

Auto Transformer
fuses used on 460
volt units only.
(Hidden)

Fan Partition
Mounting
Bracket

A09199

Fig. 18 -- Blower Housing and Flue Collector Box

Compressor
Access Panel

Blower
Access
Panel

Control
Access
Panel

A09210

Fig. 19 -- Unit Access Panels

Induced Draft (combustion air) Blower Assembly

The induced--draft blower assembly consists of the inducer motor,

the blower housing, and the induced--draft blower wheel.
Clean periodically to assure proper airflow and heating efficiency.
Inspect blower wheel every fall and periodically during the heating

season. For the first heating season, inspect blower wheel
bimonthly to determine proper cleaning frequency.
To inspect blower wheel, remove draft hood assembly. Shine a

flashlight into opening to inspect wheel. If cleaning is required,
remove induced--draft blower assembly as follows:

1. Remove control access panel (See Fig. 19).
2. Remove the 5 screws that attach induced--draft blower as-

sembly to the flue collector box cover.

3. Slide the assembly out of the unit. (See Fig. 20). Clean the

blower wheel. If additional cleaning is required, continue

with Steps 4 and 5.

4. To remove blower wheel, remove 2 setscrews.
5. To remove inducer motor, remove screws that hold the

inducer motor to the blower housing.

6. To reinstall, reverse the procedure outlined above.

Flue Gas Passageways

To inspect the flue collector box and upper areas of the heat

exchanger:

1. Remove the induced draft blower assembly according to

directions in the Induced Draft Blower Assembly section.

2. Remove the 11 screws holding the flue collector box cover

(See Fig. 18) to the heat exchanger assembly. Inspect the
heat exchangers.

3. Clean all surfaces, as required, using a wire brush.

Limit Switch

Remove blower access panel (see Fig. 19). Limit switch is located

on the fan partition.

Burner Ignition

Unit is equipped with a direct spark ignition 100 percent lockout

system. Ignition module (IGC) is located in the control box (See

Fig. 18). Module contains a self--diagnostic LED. During
servicing, refer to label diagram or Table 5 in these instructions for

LED interpretation.
If lockout occurs, unit may be reset by either momentarily

interrupting power supply to unit or by turning selector switch to
OFF position at the thermostat.

Main Burners

At the beginning of each heating season, inspect for deterioration

or blockage due to corrosion or other causes. Observe the main
burner flames and adjust, if necessary.
Removal of Gas Train
To remove the gas train for servicing:

1. Shut off main gas valve.
2. Shut off power to unit and install lockout tag.
3. Remove control access panel (See Fig. 19).
4. Disconnect gas piping at unit gas valve.
5. Remove fan partition mounting bracket (2 screws located

on the left side of control compartment on the fan partition

panel). Slide bracket forward, bottom first to remove. (See
Fig. 18).

6. Remove wires connected to gas valve. Mark each wire.
7. Remove ignitor and sensor wires at the ignitor module.
8. Remove the mounting screw that attaches the burner rack to

the unit base (See Fig. 18).

9. Slide the burner rack out of the unit (See Fig. 18 and 21).

10. To reinstall, reverse the procedure outlined above.

Outdoor Coil, Indoor Coil, and Condensate Drain Pan

Inspect the outdoor coil, indoor coil, and condensate drain pan at

least once each year. The coils are easily cleaned when dry;
therefore, inspect and clean the coils either before or after each

cooling season. Remove all obstructions, including weeds and
shrubs, that interfere with the airflow through the condenser coil.
Straighten bent fins with a fin comb. If coated with dirt or lint,

clean the coils with a vacuum cleaner, using the soft brush
attachment. Be careful not to bend the fins. If coated with oil or

grease, clean the coils with a mild detergent--and--water solution.
Rinse coils with clear water, using a garden hose. Be careful not to

splash water on motors, insulation, wiring, or air filter(s). For best

results, spray outdoor coil fins from inside to outside the unit. On
units with an outer and inner condenser coil, be sure to clean

between the coils. Be sure to flush all dirt and debris from the unit
base.
Inspect the drain pan and condensate drain line when inspecting

the coils. Clean the drain pan and condensate drain by removing all
foreign matter from the pan. Flush the pan and drain tube with

clear water. Do not splash water on the insulation, motor, wiring, or
air filter(s). If the drain tube is restricted, clear it with a “plumbers

snake” or similar probe device. Ensure that the auxiliary drain port
above the drain tube is also clear.

48V

T

--

A

Advertising