NOTE: This heater has a continuous fan-only feature. See

page 3 for details.

Installation of Recessed Back Box

in New Construction

1. Mounting Back Box (See Figure 1).

a. Place the back box between two 16" (406 mm) center-to-

center wall studs at the desired mounting height but no

closer than 8" (203 mm) to adjacent wall or floor.

Note: If wall studs are spaced greater than 16” on center, addi-

tional framing supports may be necessary.

b. Align back box such that the bottom and sides will be

flush with finished wall surface (top flange of back box

should protrude approximately 1/2" (12.7 mm) from fin-

ished wall surface).

c. Secure the back box in position with wood screws or nails

as shown in Figure 1.

2. Power Supply Wiring (See Figure 1)

NOTE: Wire compartment volume - 119in

3

(1950cm

3

).

a. Run a power supply cable into the knockout area in the

upper right hand corner of the back box. All wiring must be

in accordance with National and Local Electrical Codes.

Refer to Table 1 for correct wire size.

b. Remove disconnect switch bracket by loosening two

screws on the right side.

c. Install a cable clamp in the “knockout” in the top of the

back box.

d. Insert power supply cable through cable clamp, allowing at

least 6" (152mm) of leads to extend inside the back box.

Connect the blue lead wires of disconnect switch to the

supply wire leads using wire connectors (see wiring dia-

gram, pg. 3.)

e. Ground the back box by connecting the supply ground lead

wire to the green ground screw located in the inside top of

the back box.

f. Secure disconnect switch bracket in place by tightening

screws.

Installation of Recessed

Back Box in Existing Construction

1. Provide a wall opening 14-1/2" (362mm) wide by 18-1/2"

(470mm) high at the desired mounting height, but no closer

than 8" (203mm). (See Figure 2.)

Note: Locate so at least one side of opening is at wall stud.
2. Power Supply Wiring

NOTE: Wiring Compartment Volume - 119in

3

(1950cm

3

).

a. Run a power supply cable into the area above the top of the

wall opening. All wiring must be in accordance with National

and Local electrical codes. Refer to Table 1 for correct wire

size.

b. Remove disconnect switch bracket by loosening the two

screws on the right side.

c. Install a cable clamp in the “knockout” in the top of wall

back box.

d. Insert power supply cable through cable clamp, allowing

approximately 6" (152mm) of cable length to remain inside

the back box to facilitate connections.

3. Mounting Back Box

a. Place the back box into wall opening flush with finished

wall surface on bottom and sides of box. (Top flange of

backbox should protrude approximately 1/2" or 12.7mm

from finished wall surface).

b. Secure the back box in place with wood screws or nails.

4. Wiring Disconnect Switch

a. Connect the power supply wires to the blue wires of the

disconnect switch using wire connectors (see wiring dia-

gram, pg. 3)

b. Ground the back box connecting the supply ground lead

wire to the green ground screw located in the inside top of

the back box.

c. Secure disconnect switch bracket in place by tightening

screws.

Fig. 1: Locating Recessed Back Box in New Construction

Fig. 2: Locating Recessed Back Box in Existing Construction

2

BACK BOX

BACK BOX

TABLE 1

MMIINN.. SSUUPPPPLLYY

CATALOG

WIRE

NUMBER

VOLTS PHASE

WATTS

AMPS

GAUGE

CWH3150

120

1

1500

12.5

12

CWH3180

120

1

1800

15.0

12

CWH3404*

240/208

1

4000/3000 16.7/14.5

10

2000/1500

8.3/7.2

12

CWH3407*

277/240

1

4000/3000 14.5/12.5

12

2000/1500

7.2/6.3

12

CWH3307*

277

1

3000/1500 10.8/5.4

14

CWH3408*

208

1

4000/2000 19.2/9.6

10

CWH34083

208

3

4000

11.1

14

CWH34043

240

3

4000

9.7

14

CWH3504

208/240

1

3600/4800 17.3/20.0

10

CWH3507

240/277

1

3600/4800 15.0/17.3

10

CWH3508

208

1

4800

23.1

10

CWH35083

208

3

4800

13.4

12

CWH35043

240

3

4800

11.6

14

CWH3203

347

1

2000

5.8

14

CWH3206

600

1

2000

3.3

14

CWH3153

347

1

1500

4.3

14

CWH3156

600

1

1500

2.5

14

CWH3303

347

1

3000

8.6

14

CWH3306

600

1

3000

5

14

CWH3403

347

1

4000

11.5

14

CWH3406

600

1

4000

6.7

14

CWH3503

347

1

4800

13.8

12

CWH3506

600

1

4800

8

14

* Factory wired for higher wattage. Field convertible to half wattage.