Qmark MUH - Horizontal / Downflow Unit Heaters User Manual

Electrical accessories

Advertising
background image

3. Install leads to terminal block. Refer to wiring diagram, Figure 6, for

wiring procedure on 3KW and 5KW units (208V, 240V, and 277V

only). Refer to wiring diagram, Figure 7, for wiring procedure on all

other heaters.

INSTALLATION OF REMOTE FAN SWITCH

RFS1

The Remote Fan Switch is mounted external and remote from the unit

heater. The voltage of the remote fan switch circuit is the same as the

supply voltage to the heater.
1. Use 14 gauge copper, NEC Class 1, 600V rated insulated wire.

Wiring must meet all local and NEC requirements.

2. Install the remote fan switch in a standard wall box in any conve-

nient location that is protected from traffic or other accidental dam-

age.

3. Connect the 14 gauge copper field wire to the switch lead wires with

suitable connectors.

4. A 1/2-inch (12.7mm) knockout is provided in the back of the heater

adjacent to the control terminal board. Use a crimp-on terminal suit-

able for No. 8 screw on the control terminal board. Connect one field

wire terminated lead to terminal F1 and the other terminated lead to

terminal F2. Refer to Figure 6 for connecting to heaters without built-

in contactors. Refer to Figure 7 for connecting to heaters equipped

with built-in contactors.

INSTALLATION OF REMOTE PILOT DUTY FAN

SWITCH RFS2 (Including Wall Switch and Relay)

The Remote Fan Switch is mounted external and remote from the unit

heater.
1. Use 18 gauge (min.), NEC Class 1, 600V wiring that meets all local

and NEC requirements.

2. Install the remote fan switch in a standard wall box in any conve-

nient location that is protected from traffic or other accidental dam-

age.

3. Connect the field wire to the switch lead wires with suitable connec-

tors.

4. A 1/2-inch (12.7mm) knockout is provided in the back of the heater

adjacent to the control terminal board. Use a crimp-on terminal

suitable for No. 8 screw on the control terminal board. Connect one

field wire terminated lead to terminal "R" and the other terminated

field wire lead to terminal "G". Refer to Figure 7.

5. Install relay as indicated below.

INSTALLATION OF FAN RELAY (For RFS2)

1. Mount relay in control compartment with two No. 8 mounting screws

as shown in Figure 4.

2. Connect the lead wires from the relay to the control terminal board

as shown in Figure 7. Each lead wire is marked for proper terminal

location; connect the lead wires as indicated.

INSTALLATION OF INTERNAL THERMOSTAT

MT1, MT2, 2E569, 3UG72 2YU33 and 2YU95

1. Remove 5/16" (7.9mm) knockout from back of heater and route cap-

illary tube through hole (Figure 1).

2. Install thermostat bulb clip in slot provided in the back panel of the

heater. Secure capillary bulb in clip.

3. Press on left side of logo label on front of heater to locate shaft and

screw holes. Punch holes through label.

4. Install thermostat as shown in Figure 2, coiling any excess capillary

tubing inside the heater.

5. Refer to wiring diagram, Figure 6, for wiring procedure on 3KW and

5KW (208V, 240V and 277V only). Refer to wiring diagram, Figure

7, for wiring procedure on all other heaters.

6. Remove backing from label (supplied) and install over thermostat

shaft. Install knob by pushing onto the thermostat shaft.

THERMOSTAT
BULB CLIP

5/16" (7.9mm)
DIAMETER
KNOCKOUT

BACK OF HEATER

Figure 1. Installation of Internal Thermostat Capillary

TO PREVENT POSSIBLE ELECTRICAL SHORT CIRCUIT OR

FIRE, KEEP CAPILLARY TUBING AWAY FROM INTERNAL

ELECTRICAL COMPONENTS.

WARNING

KNOB

MOUNTING
SCREWS (2)

FRONT OF
HEATER

THERMOSTAT

Figure 2. Installation of Internal Thermostat

Electrical Accessories

For MUH, HUHAA, Dayton 3UF77 - 3UF98 and

2YU58-2YU81, 3END3 and 3END4 Series Unit Heaters

INSTALLATION OF FAN SWITCH

FS, 3UG03 and 2YU82

1. Remove 1/2" (12.7mm) knockout (located between ON and AUTO)

from back of heater (Figure 3).

2. Install manual fan switch as shown in Figure 3. (Note orientation of

slot in switch nozzle. Locate slot in the switch nozzle towards the

"AUTO" position.) Be sure to use lockwasher to prevent rotation of

switch.

KNURLED
NUT

ON

AUTO

FAN
SWITCH

SLOT DOWN

HEX NUT

LOCKWASHER

BACK OF
HEATER

Figure 3. Installation of Fan Switch

F

R

O

N

T

O

F

H

E

A

T

E

R

CONTROL TERMINAL BOARD

RELAY

NO. 8
MOUNTING SCREWS

Figure 4. Installation of Fan Relay

1