INSTALLATION OF HEAT RECOVERY THERMOSTAT

HRTA, 3UG63 and 2YU90

NOTE: This accessory cannot be installed on heaters equipped

with built-in single-pole or two-stage thermostats.
(For heaters with 24 Volt Control Circuit refer to Fig. 7 and proceed

to step 1. For heaters with Line Voltage Control refer to Fig. 6 and

proceed to step 3.)
1.
Mount relay in baffle compartment with two No. 8 mounting screws

as shown in Figure 4.

2. Connect the lead wires from the relay to the control terminal board

as shown in Figure 7. Each lead wire is marked for proper terminal

location; connect lead wires as indicated.

3. Remove 5/16" (7.9mm) knockout from back of heater and route capillary

tube through hole (See Figure 1).

4. Install thermostat bulb clip in slot provided in the back panel of the

heater. Secure capillary bulb in clip.

5. Press on left side of logo label on the front of heater to locate shaft

and screw holes. Punch holes through label.

6. Install heat recovery thermostat as shown in Figure 2, coiling any

excess capillary tubing inside the heater.

7. Use the wire tie to hold the thermostat leads to other wiring at

approximately the midpoint of the leads between control terminal

board and thermostat.

8. Refer to wiring diagram, Figure 6 or Figure 7 for wiring procedure.
9. Install knob by pushing onto the thermostat shaft.
10. Set thermostat for desired turn-on temperature. Full counter-clock-

wise rotation of the knob is approximately 70°F (21° C). Full

clockwise rotation of the knob is approximately 120°F (49° C).

INSTALLATION OF 25 AMP AND 60 AMP

POWER DISCONNECT SWITCH

DS25, DS60, 3UG68, 3UG69, 2YU93 and 2YU94

1. Use copper conductor supply wire only when using these switches.
2. Remove the 5/8" (16mm) knockout and the two knockout slots from

back of heater, below OFF-ON markings.

3. Install power disconnect switch with two mounting screws as shown

in Figure 5.

4. Install the knob with the pointer position at the "OFF" position mark-

ing when the switch is rotated to the full counterclockwise position.

5. Before connecting the wires of the switch, check the pointer index.

Check to be sure the pointer end of the knob points to "OFF" when

the switch is rotated full counterclockwise. It may be necessary to

rotate the switch 180° to index the pointer knob.

6. Refer to wiring diagram, Figure 8, for wiring procedure.
(NOTE: For single-phase, remove and discard leads "L2" and "S2").

OFF

ON

MOUNTING
SCREWS (2)

POWER
DISCONNECT
SWITCH

KNOB

BACK OF
HEATER

Figure 5. Installation of Power Disconnect Switch

Figure 7. Control Terminal Board for RFS1 and RFS2

(for Heaters with Contactors)

Figure 6. Control Terminal Board

(for Heaters without Contactors)

NOTES:
1. THIS STYLE CONTROL TERMINAL BOARD USED WITH MODELS 3KW AND 5KW UNITS
(208V, 240V AND 277V ONLY).
2. WHEN UNIT IS WIRED FOR SINGLE PHASE, JUMPER H1 TO H2. IF SINGLE POLE

THERMOSTAT IS USED WITH SINGLE PHASE UNIT, CONNECT THERMOSTAT LEADS TO

P1 AND H1.
3. EXTERNAL LINE VOLTAGE THERMOSTAT SHOULD BE TREATED AS SINGLE STAGE ONLY.

S

F2

H2

F1

H1

P2

P1

RED

BLK

RED

BLK

MT-2

MT-1

2-STAGE
INTERNAL
THERMOSTAT

HEAT RECOVERY THERMOSTAT HRTA

REMOTE SUMMER FAN SWITCH RFS1

SUMMER FAN SWITCH FS (MANUAL)

T

BLACK
TO H1

RED
TO P1

OR

2E569
2YU33

3UG72
2YU95

3UG03, 2YU82

3UG63, 2YU90

Figure 8. Power Disconnect Switch Wiring Diagram for DS25,

DS60, 3UG68, 3UG69 2YU93 and 2YU94

SEE
NOTE 1

TERMINAL

BLOCK

POWER

DISCONNECT

SWITCH

S1

S2

S3

L1

L2

L3

TO
POWER
SUPPLY

SEE
NOTE 2

NOTES:
1. THIS ILLUSTRATION SHOWS WIRING HOOK UP FOR THREE PHASE

SERVICE. REMOVE LEAD WIRES MARKED L2 AND S2 WHEN USING
ONE PHASE POWER SERVICE.

2. USE COPPER SUPPLY WIRE ONLY WITH THIS SWITCH.

NOTES:
1. THIS STYLE CONTROL TERMINAL BOARD USED WITH ALL MODELS EXCEPT 3KW AND 5KW
UNITS (208V, 240V AND 277V ONLY).
2. REMOVE JUMPER W1 TO W2 WHEN 2-STAGE THERMOSTAT IS USED.
3. *ONLY ONE OF THESE ACCESSORIES MAY BE INSTALLED IN A SINGLE HEATER.
4. EXTERNAL LINE VOLTAGE THERMOSTATS SHOULD BE TREATED AS SINGLE STAGE ONLY.

REMOTE SUMMER
FAN SWITCH RFS1

S

S

*FAN RELAY (FOR HEAT RECOVERY

THERMOSTAT

HRTA OR REMOTE

PILOT DUTY FAN SWITCH RFS2)

TR

F1

W2

G

F2

W1

R

C

*SUMMER
FAN SWITCH

BLACK

RED

BLACK

RED

HEAT RECOVERY
THERMOSTAT OR
REMOTE PILOT DUTY
FAN SWITCH

T

BLACK
TO W1

T

MT-2

2-STAGE

INTERNAL

THERMOSTAT

T

RED
TO R

MT-1

2E569
2YU33

3UG72
2YU95

TO PREVENT A POSSIBLE ELECTRICAL SHORT CIRCUIT OR

FIRE, KEEP CAPILLARY TUBING AWAY FROM INTERNAL

ELECTRICAL COMPONENTS.

WARNING

6/09

ECR 38318

5200-2298-502

2