A) (b) – Qmark RCC - Cove Heaters User Manual

Page 3

Advertising
background image

{

{

Figure 5. Heater Wiring

L1

L2

N

L1

Black

Black

Black

Red

Red

Red

Red

Red

Red

White

White

White

(A) 240 / 208 VOLT HEATERS

(B) 120 VOLT OR 277 VOLT HEATERS

FOR GROUND CONTINUITY BETWEEN ADJACENT HEATERS USE GROUND WIRE PROVIDED.
SEE NOTES ABOVE FOR TWO UNIT WIRING – SUPPLY IN MIDDLE.

GROUND

* Use white cross-over
wire on the heaters
rated 120V or 277V

GROUND

TO GROUND

BLACK*

BLACK*

SUPPLY

SUPPLY

SUPPLY

GROUND

SUPPLY

(A)

(B)

GREEN
GROUND
WIRE

GREEN
GROUND
WIRE

CROSS-OVER WIRE (BLACK 208/240V, WHITE 120/277V)

FACTORY
SUPPLIED
WIRE NUTS
(5 REQUIRED)

SUPPLY

WIRING

RED CROSS-OVER WIRE USED FOR MULTIPLE END CONNECTED HEATERS ONLY.

POWER
SUPPLY

L1

ELEMENT

ELEMENT

BLACK

WHITE

RED

RED

L

N

L2

POWER
SUPPLY

ELEMENT LEAD
120V - YELLOW
208V - BLUE
240V - RED
277V - BROWN

RIGHT HAND FIELD CONNECTION SHOWN. TO WIRE ON LEFT HAND SIDE:
(1) SEPARATE ELEMENT LEAD FROM CROSS-OVER WIRE ON LEFT SIDE.
(2) USING WIRE NUT, CONNECT LEAD WIRE TO CROSS-OVER WIRE ON RIGHT SIDE.
(3) CONNECT L1 TO ELEMENT LEAD AND L2 (OR NEUTRAL) TO CROSSOVER WIRE

ON LEFT SIDE.

SEE TABLE 1 FOR EXPANSION DIMENSIONS

TWO UNIT WIRING – SUPPLY IN MIDDLE

SINGLE UNIT WIRING – SUPPLY IN MIDDLE

TWO OR MORE HEATERS – SUPPLY AT END

ALL UNITS MAY BE WIRED FROM EITHER END.
HEATER GROUNDING WIRE FOR SUPPLY
GROUND CONNECTION FOUND ON EITHER END.

WARNING: CHECK HEATER NAMEPLATE AT
INSTALLATION TO VERIFY UNIT VOLTAGE RAT-
ING IS THE SAME AS THE SUPPLY VOLTAGE.

CAUTION: TOTAL LOAD MUST NOT EXCEED
16AMPS FOR INTERCONNECTED HEATERS.

208 OR 240 VOLT MODELS

120 OR 277 VOLT MODELS