Riser diagram – Detex Delayed Egress With Magnetic Lock User Manual

Page 11

Advertising
background image

DETEX MAG LOCK SUPPLIED

WITH DETEX DELAYED EGRESS

PANIC HARDWARE

J

REFER TO WIRING &

FIRE ALARM DIAGRAMS

FOR WIRING

INSTRUCTIONS

REQUIREMENTS:

MIN. 22 GA STRANDED WIRE FOR SIGNALING

MIN. 18 GA STRANDED WIRE FOR POWER

DETEX FILTERED AND REGULATED

POWER SUPPLY WITH FIRE ALARM SYSTEM LOOP

24 VDC @1 AMP MIN

DETEX REQUIRES THE POWER SUPPLY BE LOCATED

WITHIN 40 FEET OF THE DEVICE

DOOR SIGN SUPPLIED WITH

DETEX DELAYED EGRESS

PANIC HARDWARE

DETEX DELAYED EGRESS

PANIC HARDWARE

INSTALLED BY

TRAINED TECHNICIAN

J

RISER DIAGRAM

PROVIDE WIRING CONDUIT, CONNECTOR,

ETC BETWEEN DETEX POWER SUPPLY

AND FIRE ALARM CONTROL PANEL AS

REQUIRED TO ALLOW THE FIRE ALARM

SYSTEM TO OVERRIDE THE DETEX DELAYED

EGRESS FEATURE DURING A FIRE ALARM

THE LOSS OF POWER OR OPEN FIRE

ALARM CIRCUIT WILL ELIMINATE THE

DELAY EGRESS OPERATIONS

103182 Page 11