EM ELECTRICAL OPTION

REQUIRES DETEX POWER SUPPLY

REQUIRED WIRE SIZES:

STRANDED WIRE GAUGE: 18 AWG MIN

MAXIMUM LENGTH OF TWO CONDUCTOR CABLE: 40 FEET

Power Supply with Detex Delayed Egress device

Detex requires one fire

alarm relay per power

supply

Closed Fire Alarm Loop

(must be supplied)

Door #2

(if req'd)

To Exit Device

RED/BLK WIRES

TO 24 VOLT

Orange and Blue wires to MAGNET

DO NOT ADD POWER!

(PC BOARD ASSEMBLY INSIDE

DELAYED EGRESS DEVICE)

To disable the low-battery

indication, slide the Dis Lo Bat

switch to 'ON'

RED

BLK

From (-) terminal

to pin #2 on exit

device

From (+) terminal

to pin #1 on exit

device

9V Alkaline

Battery

FACTORY INSTALLED

JUMPER

RED

BLK

Fire Loop

Sense

To Exit Device

Door #1

DETEX REQUIRES THE POWER

SUPPLY BE LOCATED WITHIN

40 FEET OF THE DEVICE

WHITE

BLACK

GREEN

RED

BLACK

RED

BLACK

103182 Page 9