KMC Controls REE-2002 User Manual

Installation guide, Connections and wiring, Power supply and e-e/i converter module

Advertising
background image

REE-2002

1

Installation Guide

Installation Guide

Mounting

1

Connections and Wiring 1
Specifications 2
Troubleshooting 2
Maintenance

2

More Information 2
Important Notices 2

Mounting

The

module may be mounted directly to a control

box surface or in a 2 x 4" electrical handy box. Add a

blank cover to conceal the module if desired.

Connections and Wiring

1. Connect a controller input to one of the three

THE-1102/REE-2002 (0–5 VDC, 0–10 VDC, 4–20

mA) outputs as shown in the sample illustration

below.

2. Connect the B, F, C, and D terminals to the

corresponding terminals on the THE-1102.

3. Supply the REE-2002 with 24 VAC (+20%/–15%)

from a Class 2 transformer (only).

Power Supply and E-E/I Converter Module

REE-2002

REE-2002

24 VAC

GND

24 VAC

0-5 VDC

0-10

VDC

4-20

mA

F

C

D

B

THE-1102

Humidity Output

(0-5 VDC)

(Without the REE-2002, only the THE-1102’s 0-5 VDC humidity

output and thermistor signal are available to a controller)

Temp. Output

(10K Thermistor)

Signal Ground

– Power Ground

+ 10-15 VDC Power

F

C

D

B

A

Controller

Temp. Input

Signal Ground

Humidity Input*

+

Phase

Neutral

*Load between Humidity Input and Signal Ground
is 250 ohms min. to 650 ohms max. for 4-20 mA
or 1000 ohms min. for VDC

NOTE: Use wire size 14 to 22 AWG, stranded.
NOTE: See also the

THE-1102 Installation Guide

for additional information about this

application. (The THE-1101 has been

discontinued.)