Wiring

Installation Guide

Relay Module, 3 Stage, Reheat

REE-4001

Mounting

Connect as shown in the sample illustration on the

next page. Supply the relay with 24 VAC, +20%/

–15%. (Use wire size of 14 to 22 AWG, stranded.)

NOT

E: The “C” terminal on these relays does

NOT denote AC Common/Neutral! “C”

is connected to the PHASE side of the 24

VAC (and the phase side is where the three

contactors are connected in “common”).

“9” is the neutral side.

NOTE: Triac s

tages 1 through 3 are for 24 VAC

loads only.

Check the graph for thermostat signal setpoints and

corresponding stages. Stage 1 turns on at 2 VDC,

Stage 2 at 4 VDC, and Stage 3 at 6 VDC. There is a

0.33 VDC switching differential on each stage.

The

REE-4001 may be mounted directly to a control

box surface or in a 2 x 4" electrical handy box. Add a

blank cover to conceal the module if desired.

Mounting

1

Wiring

1

Troubleshooting 2
Maintenance

2

Important Notices 2

REE-4001